GW5 Type serial High Voltage isolator  the series of  disconnecting switches comply with requirements in GB1985-2004.

High-voltage Alienating Disconnecting Switches and Earthing Switches,IEC62271-102:2002AC Disconnecting Switches and Earthing Switches ,and IEC60694:1996 Common Clause for High voltage Switchgear and Control Devices.

Product feature

1.Complete in specifications,high technical parameters is high, wide range. Additional, wide scope of application , it can be used for high layout. Installation way is flexible.

2.Perfect sealing Performance and  Resistant To Rust

3.Simple, reliable mechanical rotating way.

4.Perfect dustproof, waterproof, and anti-corrosion ability.

5.Full set of steel galvanized foundation frame and the vertical and horizontal  dwang for option.

Service Conditions:

? Altitude:1000m~3000m

?Ambient temperature:-30°C ~-40°C

?Wind pressure:≤700pa(wind speed 34m/s)

?Earthquake intensity:≤8 degree

?Rative humidity of air:monthly≤90°C,daily≤95°C

?Environment degree: degree III

?Cannot be use on the condition of the danger of fire and blast,heavy pollution,chemical etching,strong shake ect.

Technical parameter

No Items Technical parameter
1 Rated Voltage                         kV 33 ,35,36,40.5 72.5
2 Nominal system   voltage         kV 35 66
3 Rated   current           A 630;1250;1600;2000;2500;3150;4000
4 Rated Short Time withstand current and   Time            kA/s 25~50/4
5 Rated Peak withstand   current                kA 63~125
6 1min power frequency  withstand   voltage (effective value)    kV To earth 95/85 140
To phase 95/85 140
Across Isolating DS 118 180
7 Lightning Impulse wishstand voltage(peak   value) KV To earth 185 325
To phase 185 325
Across Isolating DS 210 385
8 Rated mechanical terminal load              N Level of lateral load 500 750
Level of vertical load 250 500
Vertical 500 750
9 The min distance of insulation against   ground      mm 300 500
10 Max Man Operative Moment            N. m 200
11 Motor Drive operating mechanism control   voltage                   V AC220,380; DC110,220
12 Motor Drive operating mechanism motor    voltage                      V AC220,380; DC110,220